| INPUT |
SPECIFICATIONS |
| Low Voltage Range |
Nominal 120V (-25%+15%) and / or |
| High Voltage Range |
Nominal 230V (-25%+15%) w/o battery |
| Frequency |
50/60Hz Auto-select ± 3Hz (Programmable) |
| Generator Input |
Fully compatible with AC Generators |
| PFC Input |
Power Factor Correction-Option (0.99) |
| OUTPUT |
|
| Waveform |
Pure Sinewave with <5% THD |
| Power Rating |
Refer to Model and Rating Chart Below |
| Selectable Outputs |
100V,115V,120V or 220V, 230V, 240V |
| Voltage Regulation |
±3% or better |
| Frequency on AC |
Normally synchronized to utility |
| Frequency Conversion |
Freq.(& voltage) conversion - optional |
| Frequency on Battery |
±0.3% for either 60 Hz or 50 Hz |
| Crest Factor |
3 to 1 |
| Transfer Time |
ZERO, True On-Line Design |
| Surge Protection |
480 Joules (Typical) |
| Lightning Protection |
6500A, ANSI C62.41 / IEEE 587 A & B |
| PHYSICAL |
|
| Dimensions |
Refer to Product Data Sheet for each model |
| Temperature |
0 to 40C |
| Humidity |
0% to 95% Non-Condensing |
| Communications |
RS232, Relay contacts, EPO, SNMP |
| RS232 Baud Rates |
1200, 2400, 4800 or 9600 Baud (selectable) |
| Power Connections |
Four to Six output receptacles |
| Colors |
Charcoal Gray or Beige are standard |
| Agencies |
UL FCC, CE Mark |